MG High Temperature Lead Wire


High Temperature Lead Wire:

600 Volts, 450C, 20 AWG - 500 MCM.

Conductor:

Flexible stranded 27% nickel plated, annealed copper.

Sizes:

20 AWG - 500 MCM.

Insulation:

Glass reinforced phlogopite mica tapes. A fiberglass braid jacket is applied over the insulation, then treated with a high temperature saturant. Natural color is tan. Other colors available on request.

Applications:

Used for internal wiring of domestic and commercial ovens as well as cooking appliances. Also ideal for use in electric heaters and for equipment wiring in iron mills, glass plants and cement kilns.

Approvals:

UL Style as listed. CSA AWM Class I - Group A/B

 

AWG Stranding Insulation Thickness Braid
Thickness
Overall
Diameter
Amps Weight
Lbs / Mft
Temperature
Rating
20 10/.0100 0.025 .007 0.105 23 10 450°C
18 16/.0100 0.025 .007 .0115 31 12 450°C
16 26/.0100 0.025 .007 0.125 40 16 450°C
14 41/.0100 0.025 .007 0.140 55 23 450°C
12 65/.0100 0.025 .007 0.160 75 31 450°C
10 105/.0100
0.030 .017 0.210 100
52 450°C
8 133/.0111 0.030 .017 0.265 130 78 450°C
6 133/.0142 0.030 .017 0.310 175 115 450°C
4 133/.0177 0.030 .017 0.365 235 175 450°C
2 133/.0223 0.035 .020 0.450 315 260 450°C
1 259/.0177 0.035 .020 0.490 420
320 450°C
1/0 259/.0202 0.035 .020 0.535 490 400 450°C
2/0 259/.0229 0.035 .020 0.590 580 505 450°C
3/0 259/.0255 0.035 .020 0.650 675 620 450°C
4/0 259/.0286 0.035 .020 0.710
785 760 450°C
250 MCM 427/.0255 0.040 .020 0.775 865 915 450°C
350 MCM 427/.0286 0.040 .020 0.890 1075 1250 450°C
500 MCM 427/.0342 0.040 .020 1.045 1400 1770 450°C